TMP-01 × FUN
applies
Functional · Accuracy ±1 °C
Why this dot
A normal reading must match a reference thermometer.
Technique
Equivalence class: one value inside the range.
Test cases
TMP-01 × NEG
not applicable
Negative · Accuracy ±1 °C
Why no test here
Accuracy has no invalid input. Invalid temperatures live in TMP-06.
TMP-01 × BND
applies
Boundary · Accuracy ±1 °C
Why this dot
Every number in a requirement creates a boundary dot.
Technique
Boundary value analysis on both range edges.
Points
lower edge: -19.9 · -20.0 · -20.1 °C · upper edge: 84.9 · 85.0 · 85.1 °C
Test cases
Depends on open questions: Q9, Q10
TMP-01 × CFG
not applicable
Configuration · Accuracy ±1 °C · proposed
Why no test here
The only configuration in bench 1 is the supply level, run in TMP-05 CFG.
TMP-01 × CMP
not applicable
Compatibility · Accuracy ±1 °C
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-01 × CPL
not applicable
Compliance · Accuracy ±1 °C · proposed
Why no test here
No standard or external clause applies beyond the requirement text.
TMP-01 × PRF
applies
Performance · Accuracy ±1 °C
Why this dot
Accuracy is a performance number with a tolerance.
Technique
Sweep across the range against a reference.
Points
sweep edges: -20 · 85 °C
Test cases
TMP-01 × STR
applies
Stress and soak · Accuracy ±1 °C
Why this dot
Drift shows up only in long runs.
Technique
Soak at a constant temperature.
Test cases
TMP-01 × FI
not applicable
Fault injection and power loss · Accuracy ±1 °C · proposed
Why no test here
Accuracy has no fault of its own. Sensor faults are TMP-07.
TMP-01 × SEC
not applicable
Security · Accuracy ±1 °C
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-01 × UPG
not applicable
Upgrade and recovery · Accuracy ±1 °C · proposed
Why no test here
No firmware update in bench 1. Readings after a sensor fault are TMP-07 UPG.
TMP-01 × OBS
not applicable
Observability · Accuracy ±1 °C · proposed
Why no test here
The reading itself is the observable output. There is no extra state to expose.
TMP-02 × FUN
applies
Functional · Period 1000 ± 50 ms
Why this dot
A message must arrive every period.
Technique
Count messages over a fixed window.
Points
period limits: 950 · 1050 ms
Test cases
TMP-02 × NEG
not applicable
Negative · Period 1000 ± 50 ms · proposed
Why no test here
The device only sends (Q18 assumed), so the period has no invalid input.
Depends on open questions: Q18
TMP-02 × BND
not applicable
Boundary · Period 1000 ± 50 ms
Why no test here
The period tolerance is checked in PRF, not as an input boundary.
TMP-02 × CFG
not applicable
Configuration · Period 1000 ± 50 ms · proposed
Why no test here
The only configuration in bench 1 is the supply level, run in TMP-05 CFG.
TMP-02 × CMP
not applicable
Compatibility · Period 1000 ± 50 ms
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-02 × CPL
not applicable
Compliance · Period 1000 ± 50 ms · proposed
Why no test here
No standard or external clause applies beyond the requirement text.
TMP-02 × PRF
applies
Performance · Period 1000 ± 50 ms
Why this dot
After Q1 the period has a tolerance, so it can fail.
Technique
Timestamp consecutive messages, check 950 to 1050 ms.
Points
period limits: 950 · 1050 ms
Test cases
TMP-02 × STR
applies
Stress and soak · Period 1000 ± 50 ms
Why this dot
Timers can slip after hours of running.
Technique
Soak with a histogram of periods.
Points
period limits: 950 · 1050 ms
Test cases
Depends on open questions: Q11
TMP-02 × FI
gap
Fault injection and power loss · Period 1000 ± 50 ms · proposed
Why there is no test yet
The period during ERR SENSOR or ERR RANGE has no expected result until Q13 is answered.
Risk
During a fault the device may flood the line or go silent, and the host times out.
Accepted
Until Q13 is answered a period check during errors would test a guess, not the spec. The errors themselves are R2 and R3.
Depends on open questions: Q13
TMP-02 × SEC
not applicable
Security · Period 1000 ± 50 ms
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-02 × UPG
not applicable
Upgrade and recovery · Period 1000 ± 50 ms · proposed
Why no test here
No firmware update in bench 1, and the period has no error state of its own.
TMP-02 × OBS
not applicable
Observability · Period 1000 ± 50 ms · proposed
Why no test here
The message stream itself shows the period. There is no extra state to expose.
TMP-03 × FUN
applies
Functional · Message format
Why this dot
Every message must parse.
Technique
A regex runs on every message of every test, a free check.
Test cases
Depends on open questions: Q14
TMP-03 × NEG
not applicable
Negative · Message format · proposed
Why no test here
The device only sends (Q18 assumed), so the format has no invalid input. FUN-01 parses every message.
Depends on open questions: Q18
TMP-03 × BND
applies
Boundary · Message format · proposed
Why this dot
Rounding decides the integer on the line, and off-by-one bugs sit at the half degree.
Technique
Boundary values on the rounding edges from the Q9 and Q14 assumptions, one input step either side.
Points
half degree: 80.4 · 80.5 · 80.6 °C · half degree below zero: -0.6 · -0.5 · -0.4 °C
Test cases
Depends on open questions: Q9, Q14
TMP-03 × CFG
not applicable
Configuration · Message format · proposed
Why no test here
The only configuration in bench 1 is the supply level, run in TMP-05 CFG.
TMP-03 × CMP
not applicable
Compatibility · Message format
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-03 × CPL
applies
Compliance · Message format
Why this dot
The format is a spec clause, including the minus sign.
Technique
Clause check against the spec text.
Points
lower edge: -20 °C
Test cases
TMP-03 × PRF
not applicable
Performance · Message format · proposed
Why no test here
The format has no timing or throughput number.
TMP-03 × STR
not applicable
Stress and soak · Message format · proposed
Why no test here
FUN-01 checks the format of every message, the 12 h soaks included.
TMP-03 × FI
not applicable
Fault injection and power loss · Message format · proposed
Why no test here
No fault changes the format rule. Faults are TMP-05 and TMP-07.
TMP-03 × SEC
not applicable
Security · Message format
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-03 × UPG
not applicable
Upgrade and recovery · Message format · proposed
Why no test here
No firmware update in bench 1, and the format has no error state of its own.
TMP-03 × OBS
not applicable
Observability · Message format · proposed
Why no test here
The message is the output. There is nothing more to observe.
TMP-04 × FUN
applies
Functional · LED 80 / 78 °C
Why this dot
The LED is the alarm the user actually sees.
Technique
One value above the threshold inside the range, one far below.
Test cases
Depends on open questions: Q16
TMP-04 × NEG
applies
Negative · LED 80 / 78 °C
Why this dot
Noise around the threshold must not make the LED flicker.
Technique
Error guessing: oscillate the input around the threshold.
Test cases
TMP-04 × BND
applies
Boundary · LED 80 / 78 °C
Why this dot
Two thresholds: 80 on the way up, 78 on the way down.
Technique
Boundary values plus state transitions, because hysteresis has a direction.
Points
rising: 79.9 · 80.0 · 80.1 °C · falling: 78.1 · 78.0 · 77.9 °C
Test cases
Depends on open questions: Q9, Q16
TMP-04 × CFG
not applicable
Configuration · LED 80 / 78 °C · proposed
Why no test here
The only configuration in bench 1 is the supply level, run in TMP-05 CFG.
TMP-04 × CMP
not applicable
Compatibility · LED 80 / 78 °C
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-04 × CPL
not applicable
Compliance · LED 80 / 78 °C · proposed
Why no test here
No standard or external clause applies beyond the requirement text.
TMP-04 × PRF
not applicable
Performance · LED 80 / 78 °C · proposed
Why no test here
The requirement has no LED timing number, and LED logic has no load dimension.
TMP-04 × STR
not applicable
Stress and soak · LED 80 / 78 °C · proposed
Why no test here
LED logic has no load dimension. Drift is covered by TMP-01 soak.
TMP-04 × FI
not applicable
Fault injection and power loss · LED 80 / 78 °C
Why no test here
LED driver faults are hardware, out of scope for the simulator. Listed in the STP under Not tested.
TMP-04 × SEC
not applicable
Security · LED 80 / 78 °C
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-04 × UPG
gap
Upgrade and recovery · LED 80 / 78 °C · proposed
Why there is no test yet
The LED state at power-up, during ERR messages and after recovery is undefined until Q12 is answered.
Risk
After a reset or an error the LED may show a stale alarm or miss a real one.
STP risk
R1
Depends on open questions: Q12
TMP-04 × OBS
not applicable
Observability · LED 80 / 78 °C · proposed
Why no test here
The LED is itself the observable state.
TMP-05 × FUN
not applicable
Functional · Supply 4.75 to 5.25 V · proposed
Why no test here
Normal operation at 5.00 V is part of the CFG smoke set.
TMP-05 × NEG
not applicable
Negative · Supply 4.75 to 5.25 V · proposed
Why no test here
Supply outside the band is checked in BND and FI.
Depends on open questions: Q15
TMP-05 × BND
applies
Boundary · Supply 4.75 to 5.25 V
Why this dot
Just outside the band the output must not turn into garbage.
Technique
Boundary values on voltage.
Points
low edge: 4.8 · 4.75 · 4.7 V · high edge: 5.2 · 5.25 · 5.3 V
Test cases
Depends on open questions: Q15
TMP-05 × CFG
applies
Configuration · Supply 4.75 to 5.25 V
Why this dot
The supply level is a configuration of the environment.
Technique
Run the smoke set at each supply level.
Points
supply band edges: 4.75 · 5.25 V
Test cases
TMP-05 × CMP
not applicable
Compatibility · Supply 4.75 to 5.25 V
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-05 × CPL
not applicable
Compliance · Supply 4.75 to 5.25 V · proposed
Why no test here
No standard or external clause applies beyond the requirement text.
TMP-05 × PRF
not applicable
Performance · Supply 4.75 to 5.25 V · proposed
Why no test here
The supply requirement has no timing or throughput number.
TMP-05 × STR
not applicable
Stress and soak · Supply 4.75 to 5.25 V · proposed
Why no test here
The requirement names no long-run supply behaviour.
TMP-05 × FI
applies
Fault injection and power loss · Supply 4.75 to 5.25 V
Why this dot
A brownout can hit in the middle of a read.
Technique
Fault injection: short supply dip.
Test cases
Depends on open questions: Q15
TMP-05 × SEC
not applicable
Security · Supply 4.75 to 5.25 V
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-05 × UPG
not applicable
Upgrade and recovery · Supply 4.75 to 5.25 V · proposed
Why no test here
No firmware update in bench 1. Restart after a brownout is TMP-05 FI.
TMP-05 × OBS
not applicable
Observability · Supply 4.75 to 5.25 V · proposed
Why no test here
No supply monitor is specified. What the device reports outside the band waits for Q15.
Depends on open questions: Q15
TMP-06 × FUN
not applicable
Functional · Out of range · proposed
Why no test here
The normal path inside the range is TMP-01 FUN. This row is the error path.
TMP-06 × NEG
applies
Negative · Out of range
Why this dot
An out-of-range value must never be published as a reading.
Technique
Equivalence class outside the range.
Test cases
Depends on open questions: Q13
TMP-06 × BND
applies
Boundary · Out of range
Why this dot
Bugs sit right at the edges and one step outside.
Technique
Boundary values on both edges, one input step either side.
Points
upper edge: 84.9 · 85.0 · 85.1 °C · lower edge: -19.9 · -20.0 · -20.1 °C
Test cases
Depends on open questions: Q9, Q10
TMP-06 × CFG
not applicable
Configuration · Out of range · proposed
Why no test here
The only configuration in bench 1 is the supply level, run in TMP-05 CFG.
TMP-06 × CMP
not applicable
Compatibility · Out of range
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-06 × CPL
not applicable
Compliance · Out of range · proposed
Why no test here
No standard or external clause applies beyond the requirement text.
TMP-06 × PRF
not applicable
Performance · Out of range · proposed
Why no test here
The requirement has no timing number for ERR RANGE.
TMP-06 × STR
not applicable
Stress and soak · Out of range · proposed
Why no test here
The requirement names no long-run behaviour for the range check.
TMP-06 × FI
not applicable
Fault injection and power loss · Out of range · proposed
Why no test here
Out of range is a valid sensor value, not a fault. Sensor faults are TMP-07.
TMP-06 × SEC
not applicable
Security · Out of range
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-06 × UPG
applies
Upgrade and recovery · Out of range · proposed
Why this dot
A latched ERR RANGE would stop all readings until a restart.
Technique
State transition ERR RANGE to reading, timed against the TMP-02 period.
Points
period limits: 950 · 1050 ms
Test cases
Depends on open questions: Q13
TMP-06 × OBS
applies
Observability · Out of range
Why this dot
A field engineer must see why the readings stopped.
Technique
Error line on the UART. Other diagnostics wait for Q17.
Test cases
Depends on open questions: Q17
TMP-07 × FUN
not applicable
Functional · Sensor fault · proposed
Why no test here
The sensor answering is the normal path of every other row. The fault path is NEG and FI.
TMP-07 × NEG
applies
Negative · Sensor fault
Why this dot
A NACK must not leave a stale value on the line.
Technique
Error guessing from field experience.
Test cases
TMP-07 × BND
not applicable
Boundary · Sensor fault · proposed
Why no test here
The 2 s limit is a response time, checked in PRF.
TMP-07 × CFG
not applicable
Configuration · Sensor fault · proposed
Why no test here
The only configuration in bench 1 is the supply level, run in TMP-05 CFG.
TMP-07 × CMP
not applicable
Compatibility · Sensor fault
Why no test here
One sensor model and no partner devices in scope. Planned for v2 with a second sensor vendor.
TMP-07 × CPL
not applicable
Compliance · Sensor fault · proposed
Why no test here
No standard or external clause applies beyond the requirement text.
TMP-07 × PRF
applies
Performance · Sensor fault · proposed
Why this dot
The 2 s limit is a number in the requirement, so rule 3 needs a timing check.
Technique
Inject NACK faults at known moments and measure the time to ERR SENSOR.
Points
latency limit: 2 s
Test cases
TMP-07 × STR
gap
Stress and soak · Sensor fault · proposed
Why there is no test yet
No case repeats fault and recovery cycles over a long run.
Risk
A leak or a stuck state after many faults stays unseen until the field.
STP risk
R3
TMP-07 × FI
applies
Fault injection and power loss · Sensor fault
Why this dot
Faults must be injected at a known moment to be repeatable.
Technique
Simulator faults: NACK, stuck SDA, frozen value.
Points
latency limit: 2 s · latency limit: 2 s
Test cases
Depends on open questions: Q13, Q19
TMP-07 × SEC
not applicable
Security · Sensor fault
Why no test here
No command or update interface in v1, and no input on UART RX (Q18 assumed). Becomes P1 on the firmware update bench.
Depends on open questions: Q18
TMP-07 × UPG
applies
Upgrade and recovery · Sensor fault
Why this dot
Recovery: the device must heal by itself.
Technique
State transition ERROR → NORMAL.
Points
resume limit: 2 s
Test cases
Depends on open questions: Q8
TMP-07 × OBS
applies
Observability · Sensor fault
Why this dot
The error must be visible and tell its cause.
Technique
Error line on the UART. Other diagnostics wait for Q17.
Test cases
Depends on open questions: Q17